Cranage LISN Model VN1-100S Two Line V-Network |
|
| General A LISN is used in conjunction with a spectrum
analyser or receiver for measuring high frequency noise conducted on
AC/DC power lines. It is located between the incoming supply and the
Equipment Under Test (EUT). In addition to complying with CISPR16 specifications
for the industrial, residential, and commercial environments, the Cranage
VN1-100S LISN contains a bi-directional transient voltage limiter and
wideband power attenuator which prevents front-end damage to receivers
and analysers. |
|
| Current
range: Voltage range: Network parameters: Line Frequency range: Earth Leakage current: Connectors: Controls: Indicators: RF output: Insertion Loss: Transient Protection Level: Op. Temperature: Dimensions: Construction: |
up to 100A rms
AC/DC max. up to 275V rms AC/DC max. 50W / 50mH dc to 100Hz 80mA (typ) @50Hz Line (input): 6mm shrouded 'snap-lock' (L, E, N) EUT (output): 6mm shrouded skts (L, E, N) Control: IEC/CEE22 input 240/120V AC 50/60Hz BNC: RF outputs (L, N), internally terminated at 50 ohms Line Monitor: push-button for selecting L or N Red LED indicates control circuit 'ON' Yellow LED's indicate monitored line 150kHz to 30MHz (Band B CISPR16 compliant) 0dB 150dBmV -5 to +45 deg. C 295(H) x 530(W) x 422(D)mm aluminium alloy instrument case, side extrusions incorporate carrying flange |
| Warranty
on Lisns All parts on these products are warranted by the manufacturer: Cranage EMC Technology Limited, Stable Court, Oakley, Nr. Market Drayton, Shropshire TF9 4AG: against defects in materials or workmanship for a period of 12 months from the date of purchase. |
|